MATRIX: Advanced Single-Phase UPS (1–3 kVA)

from €364.00

The MATRIX series delivers premium online single-phase UPS protection in a compact, high-performance design. Available in 1, 2, and 3 kVA, these systems combine advanced technology with reliability and efficiency for critical applications.

Optimised Battery Management – Fast recharge with a 1.5 A standard charger; KS version supports external battery cabinets for extended runtime.

High Efficiency – Up to 95% in Normal Mode with Power Factor 1, reducing operating costs and maximising energy use.

Reliability – Built with advanced components for long-lasting performance and significantly higher MTBF.

Smart Communication – Standard RS232 and USB ports, optional SNMP/MODBUS/AS400, plus real-time monitoring via the GTEC Explore app.

Key Features:
Power Factor 1 | Efficiency up to 95% | Cold Start | EPO Remote Control | LCD Display | Expandable Battery Options

UPS Rating:
Communication:

The MATRIX series delivers premium online single-phase UPS protection in a compact, high-performance design. Available in 1, 2, and 3 kVA, these systems combine advanced technology with reliability and efficiency for critical applications.

Optimised Battery Management – Fast recharge with a 1.5 A standard charger; KS version supports external battery cabinets for extended runtime.

High Efficiency – Up to 95% in Normal Mode with Power Factor 1, reducing operating costs and maximising energy use.

Reliability – Built with advanced components for long-lasting performance and significantly higher MTBF.

Smart Communication – Standard RS232 and USB ports, optional SNMP/MODBUS/AS400, plus real-time monitoring via the GTEC Explore app.

Key Features:
Power Factor 1 | Efficiency up to 95% | Cold Start | EPO Remote Control | LCD Display | Expandable Battery Options

Technical Specifications

MATRIX is available in the sizes 1, 2, 3, 6, 10 kVA with 1/1 configuration and in the size 10 kVA with 3/1 configuration.

Model MXT1K0MM MXT2K0MM MXT3K0MM
Power 1000 VA / 1000 W 2000 VA / 2000 W 3000 VA / 3000 W
MAIN INPUT
Grid System 1 PH + N + PE
Rated Voltage / Frequency 200/208/220/230/240 VAC (derating 10% at 208 V, derating 20% at 200 V), 50/60 Hz
Volted Range 160-300 V 100% load, 110-160 V derating to 50% load linearly
Frequency Range 40 Hz - 70 Hz (45 Hz - 55 Hz, 54 Hz - 66 Hz @ load > 60%)
Power Factor >0,99
Current THDi ><5%
OUTPUT
Rated Voltage / Frequency >200/208/220/230/240 VAC (derating 10% at 208 V, derating 20% at 200 V), 50/60 Hz
Power Factor 1
Wave Form Pure sine wave
Voltage THDv <1% (linear load); <5% (non-linear load)
Voltage Accuracy ±1%
Transient Recovery Compliant to EN62040-3 VFI-SS-313 Standard
Inverter Overload 100% < load ≤ 105%, continuous 105% < load ≤ 125%, 5 minute 125 < load ≤ 150%, 30 seconds > 150%, 500 ms
Bypass Overload 100% < load ≤ 105%, continuous 105% < load ≤ 125%, 5 minute 125 < load ≤ 150%, 30 seconds > 150%, 500 ms
Frequency Regulation (Battery Mode) 50/60 Hz ±0.1%
Crest Factor 3:1
BATTERIES
Battery Type Pb
Battery Capacity 12 V / 7 Ah 12 V / 7 Ah 12 V / 9 Ah
Number of Batteries in Series 3 6 6
Battery Rate Voltage 36 VDC 72 VDC 36 VDC
Backup Time* 7,5 min full load 10 min typical load 8 min full load 10,5 min typical load 6 min full load 9 min typical load
BATTERY CHARGER
Charging Current 1.5 A
Charging Time 3 h to recover 90% capacity
SYSTEM
Efficiency Normal operation: 91% Eco Mode operation: 96% Battery operation: 86.5% Normal operation: 94% Eco Mode operation: 97% Battery operation: 89%
Display LCD
Protection Degree IP20
Interface Standard equipment: USB, RS232, RS485, RPO, Intelligent slot Optional: SNMP, dry contacts, parallel kit, Modbus
ENVIRONMENT
Operating Temperature 0 ~ 40°C
Storage Temperature 0°C ~ 40°C (with battery, suggest to storage the battery below 25°C) -25°C ~ 55°C (without battery)
Relative Humidity 0 ~ 95% (no condensing)
Noise (dBA at 1 meter far) <45 dB <50 dB
Altitude 0 ~ 3000 m; load derated 1% per 100m, from 1000 ~ 3000m
MECHANICAL DATA
Dimensions W*D*H (mm) 145*404*220 192*428*318
Weight (KG) 12,8 26,0 26,4
Colour Black